Pulsed I/O Rate 2
30002
Pulsed I/O Rate 3
30003
Pulsed I/O Rate 4
30004
Supply Voltage
30033
30033
30033
Analog Loop Supply
30034
30034
30034
All Expansion I/O is calculated by adding the ‘Offset’ to the I/O address in the table.
The ‘Offset is calculated by multiplying the module address by 20, Eg.
Digital input #1 on an WI-I/O-EX-1-S-11 (Address 5) would be: (5x20) + 10001 = 10100
Digital output #2 on an WI-I/O-EX-1-S-11 (Address 6) would be: (6x20) + 2 = 121
Analog input #3 on an WI-I/O-EX-1-S-12 (Address 3) would be: (3x20) + 30003 = 30063.
Analog Output #7 on an WI-I/O-EX-1-S-13 (Address 7) would be: (7x20) + 40007 = 40147