“Input Registers”
Local AI1 – AI4. (Analog Inputs - Current Mode)
AI1& AI2 - 4-20mA differential, AI3 & AI4 - 4-20mA Sink
Local Supply voltage (0-40V scaling)
Local 24V loop voltage (0-40V scaling)
Local Battery voltage (0-40V scaling)
WI-I/O-EX-1-S Supply Voltage (0-40V scaling)
Local AI1 – AI4. (Analog Inputs - Voltage Mode)
AI1& AI2 - 0-20V, AI3 & AI4 - 0-5V
Local Pulse Input Rates - PI1 – PI4
Space for locally attached WI-I/O-EX-1-S Expansion I/O modules. 20
register per module address, maximum number of modules is 24
(See Appendix C: below for details)
Internal Information registers – Serial Number, Firmware Version and
Patch level
General Purpose word Storage – Used for:
Staging area for data concentrator
Fieldbus Mappings storage
Local Pulsed inputs 1-4. Big Endian Format.
Most significant word at lower / odd address.
Local Analog inputs as floating point values
Modscan Format (Sign + Exponent + Most significant 7 bits of Significand
at Even / Higher Addressed location. Lower 16 bits of Significand at lower
/ Odd addressed location)
(12.3 => 38001=CCCD, 38002=4144)
Spare space for floating point values