Equipment requirements
• A suitable current/voltage source (must be able to generate
20
.00 mA and 10.00 V to ±0.05 % or better accuracy)
• An accurate digital multimeter (accurate to 0.05 mV and ±0.1 μA)
Terminal Connections for Input calibration
Calibration Stage Signal type
Input Channel
1 2 3 4 5 6 7 8
Inputs
Signal source (+) 1 2 4 5 7 8 10 11
Signal source (−) 3 6 9 12
Input calibration procedure
1. Select the channel you wish to calibrate (see diagram above).
2. Press
ENT , display will show: Short Input 1
3
. Short the input terminals for that channel.
4. Press
ENT, Display will show Processing... message.
5
. When the display shows Input1 @ 20.00 mA connect
20.00 mA dc to the input.
6. Press ENT, Display will show Processing... message.
7
. When the display shows Input1 @ 10.00 V c
onnect
10.00 V DC to the input.
8. Press ENT, Display will show Processing... message.
9.
At the ‘Continue?’ prompt, select ‘Yes’ t
o go the next Input
Channel or ‘No‘ to go back to the calibration menu.
10. At the ‘Save?’ prompt, select ‘Yes’ t
o permanently save the
values or ‘No‘ to use the new values until next power up.