Weidmuller DPADCV - Universal glavanically isolated signal co Instrukcja Użytkownika

Przeglądaj online lub pobierz Instrukcja Użytkownika dla Sprzęt komputerowy Weidmuller DPADCV - Universal glavanically isolated signal co. Weidmuller DPADCV - Universal glavanically isolated signal converter Benutzerhandbuch Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 24
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 0
de
en
DPA/DCV 61001036/00/04.08
Bedienungsanleitung
Zweikanaliges
Grenzwertüberwachungsmodul 3
Operating instructions
Two-channel
threshold monitoring module 14
Przeglądanie stron 0
1 2 3 4 5 6 ... 23 24

Podsumowanie treści

Strona 1 - Operating instructions

deenDPA/DCV 61001036/00/04.08BedienungsanleitungZweikanaliges Grenzwertüberwachungsmodul 3Operating instructionsTwo-channel threshold monitoring m

Strona 2

10Totbandeinstellung (Regler DB)Der Totbandregler dient zum Einstellen des Schaltpunktes, bei dem der ausgelöste Alarm zurückgesetzt werden soll. Bei

Strona 3

11• ModifizierungLinke Seitenwand entfernen1. Lösen Sie die sechs mit A-F markierten Schneidklemmschrauben (zuvor Spannungsversorgung abschalten).2.

Strona 4 - Betrieb

12(Entsprechend der Schrauben G & H an der linken Seite). Merken Sie sich die Lage des Isoliermaterials.Der Zusammenbau erfolgt in umgekehrter Rei

Strona 5

13DPA-Hauptplatine und Darstellung der Steckbrücken für Relaisspulenerregung und AlarmfunktionenBrücken für die Auswahl der Relaisspulenerregung:Kanal

Strona 6 - Verdrilltes Zweidrahtkabel

14en DPA/DCVContentsOperation 15Installation 16Calibration and Setup 19Modifications 21

Strona 7

15en DPA/DCV• OperationGeneralThe DPA/DCV allows you to set two independent trip points on a DC voltage signal (typically 0-5 V). The alarm outputs ar

Strona 8 - Anschlüsse

16Sensor power supplyA 24 V DC power supply output is available on terminal 1 for light loads (it can supply currents up to 25 mA). IndicationThe fron

Strona 9

17Alarm connectionsThe DPA has a high inbuilt immunity to noise spikes caused by switching inductive loads like solenoids or relay coils. However, it

Strona 10

18Input Signal CablingUse suitable twisted pair cable for the input signal connection.ConnectionsTerminal Signal1 24 V DC (out)Input signals2 Signal +

Strona 11 - • Modifizierung

19• Calibration and SetupGeneralThe SET (setpoint) and DB (deadband) adjustments control the setpoint and hysteresis for each alarm channel. Internal

Strona 13

20Deadband (DB Control) adjustmentThe deadband control adjusts the point at which a tripped alarm resets. This point will be above the setpoint for a

Strona 14

21• ModificationsRemoving the left hand side plate1. Remove the six self tapping screws marked A-F (disconnect power first).2. Remove the two counter

Strona 15 - Operation

22DPA main board showing the locations of the high/low operation, andrelay coil energisation, selectio n jumpersRelay energisation selection jumpers:C

Strona 17

Weidmüller Interface GmbH & Co. KGPostfach 303032720 DetmoldKlingenbergstraße 1632758 DetmoldTel. +49 5231 14-0Fax +49 5231 14-20 83info@weidmuell

Strona 18 - Connections

3de DPA/DCVInhaltsverzeichnisBetrieb 4Installation 5Kalibrierung und Konfiguration 9Modifizierung 11

Strona 19 - • Calibration and Setup

4de DPA/DCV• BetriebAllgemeinDas DPA/DCV bietet die Möglichkeit, zwei unabhängige Schaltpunkte innerhalb eines DC-Spannungssignalbereichs (in der Rege

Strona 20

5SensorstromversorgungEingangsseitig steht über die Anschlussklemme 1 eine 24 V DC Spannung für die Versorgung passiver Sensoren zur Verfügung (kann

Strona 21 - • Modifications

6AnschlussbezeichnungsschildGeräte der DPA-Baureihe sind häufig individuell für spezielle Anwendungen angepasst. Entnehmen Sie daher die korrekten Ans

Strona 22

7Kabelkonfektionierung und -installationAls effektiven Schutz vor elektromagnetischer Störeinstrahlung müssen alle Signalleitungen geschirmt sein oder

Strona 23

8AnschlüsseKlemme Signal1 24 V DC (Ausgang)Eingangssignale2 Signal +3 Nicht belegt4 Signal −5Nicht belegt6789 Neutral (−)Stromversorgung10 Phase (+)11

Strona 24

9• Kalibrierung und KonfigurationAllgemeinSollwert und Hysterese der einzelnen Alarmkanäle werden über die Potentiometer SET (Sollwert) und DB (Totband

Komentarze do niniejszej Instrukcji

Brak uwag