Maximum
input range
rng=
Introduces the display range: - Next
°C °F Range Sensor
200C 392F
-99.9 to 200.0 °C or
-99.9 to 392.0 °F
Pt100
700C 1292
-200 to 700 °C or
-328 to 1292 °F
320C 608F
-80 to 320 °C or
-112 to 608 °F
Ni120
210C 410F
-80.0 to 210.0 °C or
-99.9 to 410.0 °F
Toggle Accept
Input range
IPL=
-40
Input range lower limit in display units
e.g., -40 °C
-
Dec
-
Inc
Next
Accept
IPH=
650
Input range upper limit in display units
e.g., 650 °C
-
Dec
-
Inc
Next
Accept
Damping factor
dF=
2
Introduces the damping factor
Value, e.g., 2
-
Dec
-
Inc
Next
Accept
Input
Calibration?
CIPn
CIPy
Skip input calibration
Calibrate the inputs
Toggle Accept
Important note: do not select input calibration unless you
are fully prepared to complete the entire input calibration sequence.
Enable/Disable Alarms
Alarms 1 & 2
Select
AL=Y
AL=n
Enable
Disable
Toggle Accept
Note: alarm settings are only shown if they are enabled.
Alarm channel one
Coil energisation
A1nE
A1nd
Normally energised
Normally de-energised
Toggle Accept
Alarm type
A1=L
A1=H
Low type (active below setpoint)
High type (active above setpoint)
Toggle Accept
Setpoint value
SP1=
50.0
Setpoint value
e.g., 50.00 %
-
Dec
-
Inc
Next
Accept
Deadband value
db1=
0.1
Deadband value
e.g., 0.01 %
-
Dec
-
Inc
Next
Accept
Timer delay
dL1=
20
Timer delay (set to 0s to disable)
e.g., 20 s
-
Dec
-
Inc
Next
Accept
Setup Sequence (continued)