Output calibration procedure
When the
display shows
Action/Description
ì Å
ENT
Put the instrument in setup mode and scroll through the main menu
COPn
Press Å or ì
COPy
Calibrate Outputs? Toggle Start
IP=1
Connect the multimeter to measure the output current Next
I=0
Press Å or ì. The output current should be 0.00 mA
(Use the keypad to adjust the value as required)
Increase Decrease Accept
I=20
Press Å or ì.
The output current should be 20.00 mA
Increase Decrease Accept
Measure the output voltage
E=0
Press Å or ì. The output voltage should be 0.00 V
Increase Decrease Accept
E=10
Press Å or ì. The output voltage should be 10.00 V
Increase Decrease Accept
Save
Instrument will save values and return to normal operation (using the new values).
Note: Do not remove the power while the save message is on display.
Setup Sequence
During setup the Å and ì keys change values and toggle options.
The ENT key accepts changes and moves to the next item in the setup
sequence).
Setting Display Description
Å ì
ENT
S/W Version
v4.01
S/W Version 4.01 (Note: this information only applies to versions
4.00 to 4.09)
Display and Inputs
Input type
IP=
P100
n120
Introduces the input type
Pt100 RTD sensor
Ni120 RTD sensor
Toggle Accept
Display units
dEgC
dEgF
Degrees Celsius
Degrees Fahrenheit
Toggle Accept