11 Channel one
Alarm outputs
12 Channel two
13 Common
14 Output +
Analogue outputs
15 Current −
16 Voltage −
Case Earthing is via a stud on lower side of case
Power Supply Requirements
Check the power supply against the model number before applying
power to the instrument. Micromann modules must be used with a
suitable mains Power Supply, ratings are as follows:
Voltage Range Nominal Voltage Power Frequency
100–132 V AC 110 V AC 6 VA 47-63 Hz
200264 V AC 240 V AC 6 VA 47-63 Hz
12–50 V DC* 24 V DC 6 W (at 24 V DC) -
*Using a DC power supply that provides this voltage will comply with
the instrument’s UL/CSA listing.
Connections (continued)