43
• Modifications
Analogue output type
The analogue output type (current/voltage) is set by internal push fit
jumper. To change the output type:
Ch
ange the output type push fit jumper:
1. Gently remove the backplate (it is held in place by four lugs).
2. Sl
ide the electronics from the housing.
3. Change the jumper location to the required setting (see diagram
above).
4.
Look inside the housing and note that there are connectors that
mate with the display board.
5.
Slide the electronics gently back into the case. Carefully moving the
board until the keypad connectors engage with the display board.
6. Replace the backplate.
C
h
ange the output type in the software:
1. Power up the instrument and start the setup routine.
2. W
hile the software version number is flashing, remove the security
link and press PGM.
3. T
he display will show a number as shown in the table below.
Number
0 1 2 3 4 5
Input Type mA V mA V mA V
Output type mA mA V V None None
4. Change the number to suit your input and output types.
5. Replace the security link and press PGM.
Ch
ange the output range settings:
6. Scroll through the setup and change the output type and range
settings - you will be required to calibrate the outputs.