Procedure
When the
display shows
Action/Description
Put the instrument in setup mode and scroll through the main menu
CALOut_n
Press ì or Å
CAlOut_y
Press PGM to select output calibration
Out_LO_=
Connect the multimeter to measure the output level, then press PGM
4.00
Press PGM
Measure the output signal
Adjust the output (using the ì or Å keys) until the output is at the value shown
When you are happy that the output is correct, press PGM
Out_HI_=
Press PGM
20.00
Press PGM
Measure the output signal
Adjust the output (using the ì or Å keys) until the output is at the value shown
When you are happy that the output is correct, press PGM
Save
Continue with the setup sequence.
Note: Do not remove the power while the save message is on display.
Input Calibration
Terminal Connections for Input calibration are:
Calibration Stage Signal type Terminal
mA/Voltage Signal Source
Signal + 11
Signal 10