4.5 Linearity calibration
1. Carry out a basic calibration, see above.
2. Set the selected " minimum" temperature on a PT 100 simula-
tor (when using a pr ecision resistance decade, wher e neces-
sary observe DIN IEC 751 conversion table from °C to Ω !)
and calibrate the signal conditioner output signal to 4.000 mA
using the null potentiometer.
3. Set the mean temperature "(ϑ
max
+ ϑ
min
)/2" on a PT 100 simu-
lator.
Determine the difference to the desired value:
"∆I = shown value on measuring instrument - 12.000 mA"
and calibrate the output signal to (12.000 mA - ∆I) using a
span potentiometer.
4. Set the " maximum" selected temperature ϑ
min
on the PT 100
simulator and calibrate the signal output to 20.000 mA using
the lin potentiometer.
5. Repeat steps 2 to 4 until the required accuracy is achieved.