Weidmuller PT 100/3 sig conditioners for current output Instrukcja Użytkownika Strona 6

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 14
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 5
20
2. Professionally install module.
3. Add 1 % of the temperature span to the selected "minimum"
temperature and set this value on a PT 100 simulator (when
using a precision resistance decade, where necessary ob-
serve DIN IEC 751 conversion table from °C to !) and cali-
brate the signal conditioner output signal to 0.200 mA using
the null potentiometer. (The potentiometers are located be-
hind the hinged cover).
4. Set the "maximum" selected temperature on a PT 100 simu-
lator (or precision resistance decade) and calibrate the signal
output to 20.000 mA using the Span potentiometer.
5. Repeat steps 3 and 4 (approx. 2-3 times), until the required
accuracy is achieved.
Przeglądanie stron 5
1 2 3 4 5 6 7 8 9 10 11 12 13 14

Komentarze do niniejszej Instrukcji

Brak uwag