20
Equipment requirements
• A suitable RTD Simulator
• F
lat bladed screwdriver (blade width less than 2.54 mm / 0.1 inch)
Terminal connections for calibration
Signal type Terminal
Input signal
RTD Simulator A 2
RTD Simulator B 3
RTD Simulator Bsense 4
Power supply
Neutral (−) 9
Live (+) 10
Setpoint (SET Control) adjustment
The SET controls for each channel are on the front panel of the
transmitter. For both high and low type alarms you turn the control
clockwise to trip the alarm and anticlockwise to reset it. The procedure
for adjustment is as follows:
1. Connect up the instrument according to the table above.
2. S
et the input source to the trip point.
3. Turn the SET control anti-clockwise until the LED extinguishes.
4. Slowly turn the SET control clockwise until the LED lights up.
D
eadband (DB Control) adjustment
The deadband control adjusts the point at which a tripped alarm
resets. This point will be above the setpoint for a low type alarm or
below for a high type. The procedure for adjusting the DB control is as
follows: