• Calibration and Setup
General
The SET (setpoint) and DB (deadband) adjustments control the
setpoint and hysteresis for each alarm channel. Internal jumpers
control the alarm type and relay coil energisation.
E
quipment requirements
• Two accurate decade resistance boxes. Note set Resistance box 2
to the minimum value of R2. Resistance box one is adjusted to give
the required difference signal.
F
lat bladed screwdriver (blade width less than 2.54 mm / 0.1 inch)
Note 1: Resistance box 2 can be replaced by an accurate resistor
equal to the minimum amount of R2 (the smaller resistor).
Terminal connections for calibration
Signal type Terminal
Input signal
Common 2
Resistance Box 2 3
Resistance Box 1 4
Power supply
Neutral (−) 9
Live (+) 10
Setpoint (SET Control) adjustment
The SET controls for each channel are on the front panel of the
transmitter. For both high and low type alarms you turn the control
clockwise to trip the alarm and anticlockwise to reset it. The procedure
for adjustment is as follows:
1. Connect up the instrument according to the table above.
2. S
et the inputs to the trip point.
3. Turn the SET control anti-clockwise until the LED extinguishes.
4. Slowly turn the SET control clockwise until the LED lights up.