
19
Connections
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.
S
trip wires to 7 mm from the ends. Use a suitable ferrule for multi-
stranded wires (do not solder). Use 12-28 AWG Cu Wire rated for
t
emperatures above 70 °C Only, tighten to 4.5 lb-In.
Terminal Signal
1 24 V DC (out)
Input signals
2 Current +
3 Common −
4 Voltage +
5
Not used
6
7
Link to change the set-up Security Link
8
9 Neutral −
Power supply
10 Live +
11 Channel one
Alarm outputs12 Channel two
13 Common
14 Output +
Analogue outputs15 Current −
16 Voltage −
Case Earthing is via a stud on lower side of case
Komentarze do niniejszej Instrukcji