CLC/AR 61001025/00/02.08
Bedienungsanleitung
Signalwandler mit Hilfsspannungs-
versorgung und Grenzwert-
überwachung
3
Operating instructions
Signal converter with auxiliary
voltage supply and threshold
monitoring
15
Przeglądanie stron 0
1 2 3 4 5 6 ... 27 28

Podsumowanie treści

Strona 1 - Operating instructions

deenCLC/AR 61001025/00/02.08BedienungsanleitungSignalwandler mit Hilfsspannungs- versorgung und Grenzwert- überwachung 3Operating instructionsSignal

Strona 2

10• KalibrierungAllgemeinDas CLC/AR ist werksseitig kalibriert. Eine Nachkalibrierung ist in der Regel erst im Rahmen der nächsten planmäßigen Kalibri

Strona 3

11InH=Angabe des eingangsseitigen Maximalwerts Next -20.00Stellen Sie die Signalquelle auf 20,00 mA. Calibrate -COPyFahren Sie mit der Konfigurationsse

Strona 4 - Betrieb

12• KonfigurationssequenzEinstellung Anzeige BeschreibungÅ ìENTS/W Version1.21Softwareversion 1.21 (Hinweis: Diese Informationen beziehen sich nur auf

Strona 5 - Å und ì

13Alarme aktivieren/deaktivierenAlarms 1 & 2 SelectAL=YAL=nAktivierenDeaktivierenToggle AcceptHinweis: Die Alarmeinstellungen werden nur angezeigt

Strona 6

14Analoge AusgängeAnalogeOutput typeOP=IOP=EAnaloger StromausgangAnaloger SpannungsausgangToggle AcceptAnalogue Output RangeOPL=4.00Minimaler Ausgangs

Strona 7

15en CLC/ARContentsOperation 16Setup Changes 21Calibration 22Setup Sequence 24

Strona 8 - Verteilung der Breakpoints

16en CLC/AR• OperationGeneralThe CLC/AR is a DIN rail mount, curve linearising/characterising signal converter for current/voltage signals. It also in

Strona 9 - • Konfigurationsänderungen

17Reviewing the setupFor review mode, press the Å and ì keys simultaneously. Press the Å and ì keys to move through the setup sequence (see table). Gr

Strona 10 - • Kalibrierung

18Power Supply RequirementsCheck the power supply against the model number before applying power to the instrument. Micromann modules must be used wit

Strona 11

19ConnectionsFor effective protection from electromagnetic noise, all signal cables must be shielded, or located on conductive trays or in conduits. S

Strona 13

20Curve suitable for fixed input interval breakpoint linearisation.Curve suitable for fixed dis play interval breakpoint linearisation .Curve suitable f

Strona 14

21• Setup ChangesChanging the setupFor setup mode, connect the security link and press the Å and ì keys simultaneously. The software version will be d

Strona 15

22• CalibrationGeneralThe CLC/AR is factory calibrated and should not require adjustment until the next scheduled calibration. However, if you require

Strona 16 - Operation

23Input calibration procedureWhen thedisplay showsAction/DescriptionENTïPut the instrument in setup mode and scroll through the main menuC PnPress Å o

Strona 17 - Å and ì keys simultaneously

24• Setup SequenceSetting Display DescriptionÅ ìENTS/W Version1.21S/W Version 1.21 (Note: this information only applies to versions 1.20 to 1.29)Disp

Strona 18

25Enable/Disable AlarmsAlarms 1 & 2 SelectAL=YAL=nEnableDisableToggle AcceptNote: alarm settings are only shown if they are enabled.Alarm channel

Strona 19

26Analogue outputsAnalogueOutput typeOP=IOP=ECurrent based outputVoltage based outputToggle AcceptAnalogue output rangeOPL=4.00Output low valuee.g., 4

Strona 21 - • Setup Changes

Weidmüller Interface GmbH & Co. KGPostfach 303032720 DetmoldKlingenbergstraße 1632758 DetmoldTel. +49 5231 14-0Fax +49 5231 14-20 83info@weidmuell

Strona 22 - • Calibration

3de CLC/ARInhaltsverzeichnisBetrieb 4Konfigurationsänderung 9Kalibrierung 10Konfigurationssequenz 12

Strona 23

4de CLC/AR• BetriebAllgemeinDer CLC/AR ist ein für die DIN-Schienenmontage geeigneter Kurvenlinearisierungs-Charakterisierungs-Signalwandler für analo

Strona 24 - • Setup Sequence

5Überschreitung des AnzeigebereichsLiegt das Eingangssignal außerhalb des programmierten Bereichs, erscheint in der Anzeige Ovr bei Bereichsüberschrei

Strona 25 - Setup Sequence (continued)

6Alarmsollwerte anpassenEinen Sollwert können Sie ändern, indem Sie die diesem Kanal zugewiesene Taste (ï für Alarm 1 oder ENT für Alarm 2) gedrückt h

Strona 26

7AnschlüsseAls effektiven Schutz vor elektromagnetischer Störeinstrahlung müssen alle Signalleitungen geschirmt sein oder in leitfähigen Kabelkanälen

Strona 27

8Typische Kurve für Breakpoint-Linearisierung mit festen EingangsintervallenTypische Kurve für Breakpoint-Linearisierung mit festen Anzeigeintervallen

Strona 28

9• KonfigurationsänderungenKonfiguration ändernZum Aufrufen des Konfigurationsmodus schließen Sie die Sicherheitsverbindung an, und drücken Sie die Tast