Weidmuller UHZAR - Universal glavanically isolated signal con Instrukcja Użytkownika Strona 18

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 24
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 17
18
• Setup Sequence
Setting Display Description
Å ì ï
ENT
S/W Version
1.31
S/W Version 1.31 (Note: this information only applies to versions
1.30 to 1.39)
Display and Inputs
Display Intensity
HIbr
LObr
High brightness
Low Brightness
Toggle Accept
Input type
Inp=
LOAC
HIAC
LOdC
HIdC
Con
SGL1
SGL2
SGL3
SGL4
Introduces input type
Low level AC signal
High level AC signal
Low level DC signal
High level DC signal
Contact Closure
Special signal - type 1
Special signal - type 2
Special signal - type 3
Special signal - type 4
Next Prev - Accept
Input frequency
range
FdP=
.
Decimal point position -
-
Shift
Next
Accept
FLO=
300
Input frequency range lower limit
e.g., 300 Hz
-
Dec
-
Inc
-
Next
Accept
FHI=
1000
Input frequency range upper limit
e.g., 1 kHz
-
Dec
-
Inc
Next
Accept
Damping factor
dF=
2
Introduces the damping factor
Value, e.g., 2
-
Dec
-
Inc
Next
Accept
Display range
ddP=
.
Decimal point position -
-
Shift
Next
Accept
dLO=
0.0
Display range lower limit
e.g., 0.0
-
Dec
-
Inc
-
Next
Accept
dHI=
100.0
Display range Upper limit
e.g., 100.0
-
Dec
-
Inc
Next
Accept
Enable/Disable Alarms
Alarms 1 & 2
Select
AL=Y
AL=n
Enable
Disable
Toggle Accept
Note: alarm settings are only shown if they are enabled.
Alarm channel one
Coil energisation
A1nE
A1nd
Normally energised
Normally de-energised
Toggle Accept
Przeglądanie stron 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 24

Komentarze do niniejszej Instrukcji

Brak uwag