Enable/Disable Alarms
Alarms 1 & 2
Select
AL=Y
AL=n
Enable
Disable
Toggle Accept
Note: alarm settings are only shown if they are enabled.
Alarm channel one
Coil energisation
A1nE
A1nd
Normally energised
Normally de-energised
Toggle Accept
Alarm type
A1=L
A1=H
Low type (active below setpoint)
High type (active above setpoint)
Toggle Accept
Setpoint value
SP1=
50.0
Setpoint value
e.g., 50.0 %
-
Dec
-
Inc
Next
Accept
Deadband value
db1=
0.1
Deadband value
e.g., 0.1 %
-
Dec
-
Inc
Next
Accept
Timer delay
dL1=
20
Timer delay (set to 0 s to disable)
e.g., 20 s
-
Dec
-
Inc
Next
Accept
Alarm channel two
Coil energisation
A2nE
A2nd
Normally energised
Normally de-energised
Toggle Accept
Alarm type
A2=L
A2=H
Low type (active below setpoint)
High type (active above setpoint)
Toggle Accept
Setpoint value
SP2=
50.0
Setpoint value
e.g., 50.0 %
-
Dec
-
Inc
Next
Accept
Deadband value
db2=
10.0
Deadband value
e.g., 10.0 %
-
Dec
-
Inc
Next
Accept
Timer delay
dL2=
20
Timer delay (set to 0 s to disable)
e.g., 20 s
-
Dec
-
Inc
Next
Accept
General alarm settings
Alarm reset
sequence
nOr
rES
Automatic reset
Manual reset
Toggle Accept
Setpoint
security
SECy
SECn
Setpoints fixed at setup
Can change setpoints
Toggle Accept
Setup Sequence (continued)